5925-01-243-4380 CIRCUIT BREAKER Index 5999-01-243-4382 WIRE MESH,KNITTED

National Stock Number:
5925-01-243-4381

Federal Supply Class:
5925

National Item Identification Number:
012434381

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
AP-7-1R-59-05181541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
POLE QUANTITY1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE50.0 MILLIAMPERES DC SINGLE LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
TERMINAL TYPE AND QUANTITY2 TAB W/SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS50.0 DC SINGLE LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS SINGLE LOCATION
RESET METHODMANUAL
BODY STYLESINGLE POLE TYPE
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING W/PANEL SEAL
UNPACKAGED UNIT WEIGHT1.800 OUNCES NOMINAL
TRIP RELEASE METHODMAGNETIC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 DC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.380 INCHES MAXIMUM
BODY LENGTH1.500 INCHES MAXIMUM
BODY WIDTH0.625 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.875 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.605 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNEF
NOMINAL THREAD SIZE0.375 INCHES
THREAD QUANTITY PER INCH32
THREAD PITCH DIAMETERS0.3503 TO 0.3537 INCHES
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE ONE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS0.5 AC AND
0.5 DC
SWITCH VOLTAGE RATING AND TYPE IN VOLTS120.0 AC AND
50.0 DC
SWITCH TERMINAL TYPEPIN
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED AND
SHOCK RESISTANT AND
VIBRATION RESISTANT
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED


Click here to Register for Free 30-day Trial