5925-01-235-0709 CIRCUIT BREAKER Index 5330-01-235-0711 GASKET

National Stock Number:
5925-01-235-0710

Federal Supply Class:
5925

National Item Identification Number:
012350710

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
504C191G2289946EATON CORPORATION
AQB-A250-175N81349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
AQBA250-175AM81349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M
MIL-C-17361/681349MILITARY SPECIFICATIONS PROMULGATED BY MILITARY DEPARTMENTS/AGENCIES UNDER AUTHORITY OF DEFENSE STANDARDIZATION MANUAL 4120 3-M


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
ARC QUENCHING METHODAIR
BODY LENGTH11.000 INCHES MAXIMUM
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH9.000 INCHES MAXIMUM
BOSS HEIGHT0.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH3.000 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH9.875 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH9.875 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH6.000 INCHES NOMINAL
FRAGILITY FACTORMODERATELY RUGGED
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDSHOCK RESISTANT AND VIBRATION RESISTANT
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE175.0 AMPERES AC AND 175.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC AND 10000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 UNTHREADED HOLE
MOUNTING SURFACE TO TERMINAL END DISTANCE9.031 INCHES NOMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS500.0 AC AND 355.0 DC ALL LOCATIONS
POLE QUANTITY3
PRECIOUS MATERIAL AND LOCATIONTERMINAL SURFACES SILVER
PRECIOUS MATERIALSILVER
RESET METHODMANUAL
SPECIAL HANDLING FEATUREMAGNETIC
SPECIFICATION/STANDARD DATA81349-MIL-C-17361 GOVERNMENT SPECIFICATION
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
TERMINAL TYPE AND QUANTITY6 THREADED STUD
TEST DATA DOCUMENT81349-MIL-C-17361 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT5.000 MINIMUM AT 200 PCT AND 15.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING50.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.250 INCHES NOMINAL


Click here to Register for Free 30-day Trial