POLE QUANTITY | 1 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 20.0 AMPERES AC SINGLE LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
TERMINAL TYPE AND QUANTITY | 2 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 115.0 AC SINGLE LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS SINGLE LOCATION |
RESET METHOD | ELECTRIC |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
MOUNTING FACILITY TYPE AND QUANTITY | 2 UNTHREADED HOLE |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
FREQUENCY IN HERTZ | 400.0 SINGLE LOCATION |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 3600.0 AC SINGLE LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP W/AUXILIARY LOAD TERMINAL AND REMOTE TRIP FEATURE SINGLE LOCATION |
AUXILIARY TRIP COIL VOLTAGE TYPE AND RATING IN VOLTS | 115.0 AC NOMINAL SINGLE LOCATION |
TRIP RELEASE DUTY CYCLE | CONTINUOUS SINGLE LOCATION |
TRIP RELEASE AMBIENT TEMP RATING | -54.0 DEG CELSIUS MINIMUM AND |
| 71.0 DEG CELSIUS MAXIMUM SINGLE LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 SINGLE LOCATION |
ULTIMATE TRIP TIME PER POLE IN SECONDS | 60.000 MAXIMUM SINGLE LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
RESET ACTUATOR VOLTAGE RATING AND TYPE IN VOLTS | 115.0 AC |
OVERALL LENGTH | 3.250 INCHES NOMINAL |
OVERALL HEIGHT | 4.250 INCHES NOMINAL |
OVERALL WIDTH | 1.250 INCHES NOMINAL |
UNTHREADED MOUNTING HOLE DIAMETER | 0.167 INCHES MINIMUM AND |
| 0.177 INCHES MAXIMUM |