5925-01-045-0149 CIRCUIT BREAKER Index 5925-01-045-0151 CIRCUIT BREAKER

National Stock Number:
5925-01-045-0150

Federal Supply Class:
5925

National Item Identification Number:
010450150

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
KA.2612588434SQUARE D CO
KA26125AB56302SQUARE D CO CEDAR RAPIDS MFG PLANT


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWOBETWEEN POLE ONE AND TWO
BODY HEIGHT4.656 INCHES NOMINAL4.656 INCHES NOMINAL
BODY LENGTH8.000 INCHES NOMINAL8.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH4.500 INCHES NOMINAL4.500 INCHES NOMINAL
BOSS HEIGHT0.156 INCHES NOMINAL0.156 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.500 INCHES NOMINAL1.500 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOFDUSTPROOF
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC AND 600.0 AC AND 250.0 DC ALL LOCATIONS250.0 DC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE1 TOGGLE
MATERIALPLASTIC CASEPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE125.0 AMPERES AC AND 125.0 AMPERES AC AND 125.0 AMPERES DC ALL LOCATIONS125.0 AMPERES DC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS25000.0 AC AND 25000.0 AC AND 22000.0 DC ALL LOCATIONS22000.0 DC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 TERMINAL4 TERMINAL
POLE QUANTITY22
RESET METHODMANUALMANUAL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT135.000 MINIMUM AT 200 PCT AND 135.000 MINIMUM AT 200 PCT AND 270.000 MAXIMUM AT 200 PCT ALL LOCATIONS270.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING40.0 CELSIUS NOMINAL ALL LOCATIONS40.0 CELSIUS NOMINAL ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONSTHERMAL-MAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT145.0 ALL LOCATIONS145.0 ALL LOCATIONS
TERMINAL TYPE AND QUANTITY2 QUICK DISCONNECT, MALE AND 2 QUICK DISCONNECT, MALE AND 2 COMPRESSION2 COMPRESSION