5925-01-031-9910 CIRCUIT BREAKER Index 5925-01-031-9912 CIRCUIT BREAKER

National Stock Number:
5925-01-031-9911

Federal Supply Class:
5925

National Item Identification Number:
010319911

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
1812320183DRS ICAS, LLC
203-22-1-61F-102-4-1-181541SENSATA TECHNOLOGIES MARYLAND, INC
203-22-2949-181541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
ACTUATOR FUNCTIONTRIP-RESETTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWOBETWEEN POLE ONE AND TWO
ARC QUENCHING METHODMAGNETIC BLOWOUTMAGNETIC BLOWOUT
BODY HEIGHT1.770 INCHES MAXIMUM1.770 INCHES MAXIMUM
BODY LENGTH2.000 INCHES NOMINAL2.000 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH1.540 INCHES NOMINAL1.540 INCHES NOMINAL
BOSS HEIGHT0.250 INCHES NOMINAL0.250 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.625 INCHES NOMINAL0.625 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS
FRAGILITY FACTORMODERATELY RUGGEDMODERATELY RUGGED
FREQUENCY IN HERTZ60.0 ALL LOCATIONS60.0 ALL LOCATIONS
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANTFUNGUS RESISTANT
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREETRIP FREE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC ALL LOCATIONS120.0 AC ALL LOCATIONS
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE1 TOGGLE
MATERIALPLASTIC CASEPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE1.0 AMPERES AC ALL LOCATIONS1.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC ALL LOCATIONS10000.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY2 CLIP2 CLIP
POLE QUANTITY22
RESET METHODMANUALMANUAL
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.050 MINIMUM AT 200 PCT AND 0.050 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT ALL LOCATIONS1.000 MAXIMUM AT 200 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONSMAGNETIC-HYDRAULIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS125.0 ALL LOCATIONS
UNPACKAGED UNIT WEIGHT8.500 OUNCES NOMINAL8.500 OUNCES NOMINAL
TERMINAL TYPE AND QUANTITY4 QUICK DISCONNECT, MALE4 QUICK DISCONNECT, MALE