| ACTUATOR FUNCTION | TRIP-RESET |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC FIRST LOCATION |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC SECOND LOCATION |
| OVERALL HEIGHT | 3.500 INCHES NOMINAL |
| OVERALL LENGTH | 9.000 INCHES NOMINAL |
| OVERALL WIDTH | 4.875 INCHES NOMINAL |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.138 INCHES |
| POLE QUANTITY | 2 |
| RESET METHOD | MANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 252.000 NOMINAL AT 125 PCT AND 20.000 MINIMUM AT 200 PCT AND 50.000 MAXIMUM AT 200 PCT AND 6.000 MINIMUM AT 300 PCT AND 10.000 MAXIMUM AT 300 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 75.0 FAHRENHEIT NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 4 SCREW |
| THREAD QUANTITY PER INCH | 32 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC) |