| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT POLE TWOAT POLE TWO |
| BODY HEIGHT | 2.125 INCHES MAXIMUM2.125 INCHES MAXIMUM |
| BODY LENGTH | 2.203 INCHES MAXIMUM2.203 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE |
| BODY WIDTH | 2.250 INCHES MAXIMUM2.250 INCHES MAXIMUM |
| BUSHING LENGTH | 0.250 INCHES NOMINAL0.250 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.188 INCHES NOMINAL1.188 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.743 INCHES NOMINAL0.743 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.812 INCHES NOMINAL1.812 INCHES NOMINAL |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.486 INCHES NOMINAL1.486 INCHES NOMINAL |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS400.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANTMOISTURE RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 120.0 AC ALL LOCATIONS120.0 AC ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH-PULL1 PUSH-PULL |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES AC ALL LOCATIONS50.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1500.0 AC ALL LOCATIONS1500.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE(S)4 THREADED HOLE(S) |
| NOMINAL THREAD SIZE | 0.138 INCHES0.138 INCHES |
| POLE QUANTITY | 33 |
| RESET METHOD | MANUALMANUAL |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT AND 10.000 MINIMUM AT 200 PCT AND 70.000 MAXIMUM AT 200 PCT ALL LOCATIONS70.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE AMBIENT TEMP RATING | 25.0 CELSIUS NOMINAL ALL LOCATIONS25.0 CELSIUS NOMINAL ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONSTHERMAL ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 138.0 ALL LOCATIONS138.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 8.000 OUNCES NOMINAL8.000 OUNCES NOMINAL |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| TERMINAL TYPE AND QUANTITY | 6 TAB W/SCREW6 TAB W/SCREW |
| THREAD QUANTITY PER INCH | 3232 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC) |