| ACTUATOR FUNCTION | TRIP-RESETTRIP-RESET |
| ACTUATOR POSITION DESIGNATION | AT EACH POLEAT EACH POLE |
| ARC QUENCHING METHOD | MAGNETIC BLOWOUTMAGNETIC BLOWOUT |
| AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM1 ALARM |
| BODY LENGTH | 2.510 INCHES MAXIMUM2.510 INCHES MAXIMUM |
| BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPEMULTIPOLE-MULTIPLE ACTUATOR TYPE |
| BODY WIDTH | 2.205 INCHES MINIMUM AND 2.205 INCHES MINIMUM AND 2.285 INCHES MAXIMUM2.285 INCHES MAXIMUM |
| BOSS HEIGHT | 0.140 INCHES NOMINAL0.140 INCHES NOMINAL |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.661 INCHES MINIMUM AND 1.661 INCHES MINIMUM AND 1.960 INCHES MAXIMUM1.960 INCHES MAXIMUM |
| CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONSOVERCURRENT ALL LOCATIONS |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.046 INCHES MINIMUM AND 2.046 INCHES MINIMUM AND 2.078 INCHES MAXIMUM2.078 INCHES MAXIMUM |
| DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL0.750 INCHES NOMINAL |
| EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKEDONE, TWO, AND THREE LINKED |
| FRAGILITY FACTOR | MODERATELY RUGGEDMODERATELY RUGGED |
| FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS60.0 ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | CORROSION RESISTANT AND CORROSION RESISTANT AND EXPLOSION RESISTANT AND EXPLOSION RESISTANT AND FUNGUS RESISTANT AND FUNGUS RESISTANT AND MOISTURE RESISTANT AND MOISTURE RESISTANT AND SHOCK RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANTVIBRATION RESISTANT |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONSSERIES TRIP ALL LOCATIONS |
| MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREETRIP FREE |
| OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 240.0 AC ALL LOCATIONS240.0 AC ALL LOCATIONS |
| MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE3 TOGGLE |
| MATERIAL | PLASTIC CASEPLASTIC CASE |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 7.0 AMPERES AC ALL LOCATIONS7.0 AMPERES AC ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC ALL LOCATIONS1000.0 AC ALL LOCATIONS |
| MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE(S)6 THREADED HOLE(S) |
| MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.800 INCHES MAXIMUM2.800 INCHES MAXIMUM |
| NOMINAL THREAD SIZE | 0.138 INCHES0.138 INCHES |
| POLE QUANTITY | 33 |
| RESET METHOD | MANUALMANUAL |
| SPECIAL HANDLING FEATURE | MAGNETICMAGNETIC |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.160 MINIMUM AT 200 PCT AND 0.160 MINIMUM AT 200 PCT AND 1.600 MAXIMUM AT 200 PCT ALL LOCATIONS1.600 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONSTIME DELAY ALL LOCATIONS |
| TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONSMAGNETIC ALL LOCATIONS |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS125.0 ALL LOCATIONS |
| UNPACKAGED UNIT WEIGHT | 0.625 POUNDS NOMINAL0.625 POUNDS NOMINAL |
| SPECIFICATION/STANDARD DATA | 81349-MIL-C-55629/6 GOVERNMENT SPECIFICATION81349-MIL-C-55629/6 GOVERNMENT SPECIFICATION |
| STORAGE TYPE | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREEINTERNAL AT POLE THREE |
| SWITCH TERMINAL TYPE | TAB, SOLDER LUGTAB, SOLDER LUG |
| SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 250.0 AC AND 250.0 AC AND 50.0 DC50.0 DC |
| SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROWSINGLE POLE, DOUBLE THROW |
| SWITCH CURRENT RATING AND TYPE IN AMPS | 10.0 AC AND 10.0 AC AND 2.0 DC2.0 DC |
| TERMINAL TYPE AND QUANTITY | 6 THREADED STUD6 THREADED STUD |
| TEST DATA DOCUMENT | 81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).81349-MIL-C-55629 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| THREAD QUANTITY PER INCH | 3232 |
| THREAD SERIES DESIGNATOR | UNIFIED NATIONAL COARSE (UNC)UNIFIED NATIONAL COARSE (UNC) |