5305-00-174-8814 SETSCREW Index 5925-00-174-8818 CIRCUIT BREAKER

National Stock Number:
5925-00-174-8815

Federal Supply Class:
5925

National Item Identification Number:
001748815

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
371D374G0479500WESTINGHOUSE ELECTRIC CORP
F202579500WESTINGHOUSE ELECTRIC CORP
S122202411660WESTINGHOUSE ELECTRIC CORP CONTROL BUSINESS UNIT
S122202479500WESTINGHOUSE ELECTRIC CORP
F202589946EATON CORPORATION


Techincal Specification:
POLE QUANTITY2
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE25.0 AMPERES AC AND
25.0 AMPERES DC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY4 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC AND
250.0 DC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL-MAGNETIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS15000.0 AC AND
15000.0 DC ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING40.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT16.000 MINIMUM AT 200 PCT AND
45.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT122.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH6.000 INCHES NOMINAL
BODY WIDTH2.750 INCHES NOMINAL
BODY HEIGHT3.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH5.188 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH1.375 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH3.375 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH1.375 INCHES NOMINAL
BOSS HEIGHT0.125 INCHES NOMINAL
UNTHREADED MOUNTING HOLE DIAMETER0.281 INCHES NOMINAL
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONBETWEEN POLE ONE AND TWO
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC


Click here to Register for Free 30-day Trial