5925-00-174-3301 CIRCUIT BREAKER Index 5925-00-174-3319 CIRCUIT BREAKER

National Stock Number:
5925-00-174-3308

Federal Supply Class:
5925

National Item Identification Number:
001743308

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
1310-87279500WESTINGHOUSE ELECTRIC CORP
25B443979500WESTINGHOUSE ELECTRIC CORP
260-0786-0013499ROCKWELL COLLINS, INC.
S06E520979500WESTINGHOUSE ELECTRIC CORP
29178899993DEPARTMENT OF THE NAVY


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE125.0 AMPERES AC AND
125.0 AMPERES DC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT FIRST LOCATION
OVERCURRENT SECOND LOCATION
UNDERVOLTAGE THIRD LOCATION
TERMINAL TYPE AND QUANTITY6 SCREW
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC AND
250.0 DC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND
TIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLERECTANGULAR DIMENSIONAL ENVELOPE
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODTHERMAL ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS10000.0 AC AND
10000.0 DC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP RELEASE AMBIENT TEMP RATING25.0 DEG CELSIUS NOMINAL ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT108.000 MINIMUM AT 200 PCT AND
500.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OVERALL LENGTH17.688 INCHES NOMINAL
OVERALL HEIGHT4.688 INCHES NOMINAL
OVERALL WIDTH8.250 INCHES NOMINAL
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.375 INCHES
THREAD QUANTITY PER INCH16
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP W/SEPARATE RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO


Click here to Register for Free 30-day Trial