6150-00-174-0869 LEAD ASSEMBLY,ELECTRICAL Index 5935-00-174-0873 CONNECTOR,RECEPTACLE,ELECTRICAL

National Stock Number:
5925-00-174-0872

Federal Supply Class:
5925

National Item Identification Number:
001740872

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
0421-374193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
70-410AMG6-3-230-474193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
GA51566L164959AMERICAN TELEPHONE AND TELEGRAPH CO
GA51566L170408AT AND T CORP
GA51566L174193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
SCC64779-180063US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR


Techincal Specification:
POLE QUANTITY2
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE3.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY4 THREADED STUD
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS230.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY4 THREADED HOLE
CASE MATERIALPLASTIC
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS2000.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT4.000 MINIMUM AT 200 PCT AND
10.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH2.490 INCHES MINIMUM AND
2.510 INCHES MAXIMUM
BODY WIDTH1.490 INCHES MINIMUM AND
1.510 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.928 INCHES MINIMUM AND
1.948 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.740 INCHES MINIMUM AND
0.760 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH2.052 INCHES MINIMUM AND
2.072 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.740 INCHES MINIMUM AND
0.760 INCHES MAXIMUM
BOSS HEIGHT0.130 INCHES MINIMUM AND
0.150 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE2.599 INCHES MINIMUM AND
2.619 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY2 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE AND TWO LINKED
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDDUSTPROOF
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
FRAGILITY FACTORMODERATELY RUGGED