POLE QUANTITY | 3 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC FIRST LOCATION |
| 30.0 AMPERES AC SECOND LOCATION |
| 50.0 MILLIAMPERES DC THIRD LOCATION |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 8 TAB, SOLDER LUG |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC FIRST LOCATION |
| 250.0 AC SECOND LOCATION |
| 30.0 DC THIRD LOCATION |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND |
| TIME DELAY ALL LOCATIONS |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 6 THREADED HOLE |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 AC FIRST LOCATION |
| 1000.0 AC SECOND LOCATION |
| 2000.0 DC THIRD LOCATION |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| SERIES TRIP SECOND LOCATION |
| RELAY TRIP THIRD LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND |
| 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BUSHING LENGTH | 0.130 INCHES NOMINAL |
BODY LENGTH | 2.000 INCHES NOMINAL |
BODY WIDTH | 2.500 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.560 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 1.660 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES NOMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.210 INCHES MAXIMUM |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 3 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, AND THREE LINKED |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | FUNGUS RESISTANT AND |
| MOISTURE RESISTANT |