5925-00-168-1288 CIRCUIT BREAKER Index 6130-00-168-1291 POWER SUPPLY

National Stock Number:
5925-00-168-1289

Federal Supply Class:
5925

National Item Identification Number:
001681289

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
333-06990073CMC ELECTRONICS INC
78-112-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
SM-A-698316-180063US ARMY COMMUNICATIONS & ELECTRONICS MATERIEL READINESS COMMAND LOGISTICS ENGINEERING DIR
AP12-4B81541SENSATA TECHNOLOGIES MARYLAND, INC
AP12-6291-181541SENSATA TECHNOLOGIES MARYLAND, INC
C79-T0190073CMC ELECTRONICS INC
SM-A-698316-190073CMC ELECTRONICS INC


Techincal Specification:
POLE QUANTITY1
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE5.0 AMPERES AC SINGLE LOCATION
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
TERMINAL TYPE AND QUANTITY2 WIRE HOOK
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS120.0 AC SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLESINGLE POLE TYPE
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING
TRIP RELEASE METHODMAGNETIC SINGLE LOCATION
FREQUENCY IN HERTZ50.0 OR
60.0 OR
400.0 SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS300.0 AC SINGLE LOCATION
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.055 MINIMUM AT 200 PCT AND
0.950 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT115.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.380 INCHES MAXIMUM
BODY LENGTH1.562 INCHES MAXIMUM
BODY WIDTH0.625 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.906 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE1.700 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNEF
NOMINAL THREAD SIZE0.375 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDHERMETICALLY SEALED
STORAGE TYPEGENERAL PURPOSE WAREHOUSE