5945-00-013-9419 RELAY,ELECTROMAGNETIC Index 5905-00-013-9425 RESISTOR,FIXED,COMPOSITION

National Stock Number:
5925-00-013-9423

Federal Supply Class:
5925

National Item Identification Number:
000139423

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
112-25-2881541SENSATA TECHNOLOGIES MARYLAND, INC
AP111-25-2881541SENSATA TECHNOLOGIES MARYLAND, INC
B30D002812464MCDONNELL DOUGLAS CORP MCDONNELL DOUGLAS ELECTRONIC SYSTEMS CO
SM333-0-75-0-75-74193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
SM333-1-75-0-75-0-75-240-400-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV


Techincal Specification:
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE750.0 MILLIAMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 WIRE HOOK
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS240.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY1 THREADED BUSHING W/PANEL SEAL
UNPACKAGED UNIT WEIGHT4.500 OUNCES NOMINAL
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
FREQUENCY IN HERTZ400.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS300.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT0.100 MINIMUM AT 200 PCT AND
0.700 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT130.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BUSHING LENGTH0.375 INCHES NOMINAL
BODY LENGTH1.495 INCHES NOMINAL
BODY WIDTH1.872 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH0.875 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.625 INCHES NOMINAL
MOUNTING SURFACE TO TERMINAL END DISTANCE1.678 INCHES NOMINAL
THREAD SERIES DESIGNATORUNEF
NOMINAL THREAD SIZE0.375 INCHES
THREAD QUANTITY PER INCH32
THREAD PITCH DIAMETERS0.3503 TO 0.3537 INCHES
MANUAL ACTUATOR TYPE AND QUANTITY1 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT POLE TWO
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND
MOISTURE RESISTANT AND
HERMETICALLY SEALED
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
PRECIOUS MATERIALSILVER
PRECIOUS MATERIAL AND LOCATIONCONTACT SURFACES SILVER
FRAGILITY FACTORMODERATELY RUGGED