POLE QUANTITY | 4 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 30.0 AMPERES AC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
TERMINAL TYPE AND QUANTITY | 10 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATION |
| TIME DELAY SECOND LOCATION |
| TIME DELAY THIRD LOCATION |
| INSTANTANEOUS FOURTH LOCATION |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 8 THREADED HOLE |
CASE MATERIAL | PLASTIC |
TRIP RELEASE METHOD | MAGNETIC-HYDRAULIC ALL LOCATIONS |
FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1500.0 AC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| SERIES TRIP SECOND LOCATION |
| SERIES TRIP THIRD LOCATION |
| RELAY TRIP FOURTH LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.600 MINIMUM AT 200 PCT AND |
| 5.000 MAXIMUM AT 200 PCT FIRST LOCATION |
| 5.000 MAXIMUM AT 200 PCT SECOND LOCATION |
| 0.600 MINIMUM AT 200 PCT AND |
| 5.000 MAXIMUM AT 200 PCT THIRD LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 2.530 INCHES MAXIMUM |
BODY WIDTH | 3.060 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 1.940 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 0.750 INCHES MINIMUM AND |
| 0.770 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.050 INCHES MINIMUM AND |
| 2.070 INCHES MAXIMUM |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 0.750 INCHES MINIMUM AND |
| 0.770 INCHES MAXIMUM |
BOSS HEIGHT | 0.150 INCHES MAXIMUM |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 2.522 INCHES MAXIMUM |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MANUAL ACTUATOR TYPE AND QUANTITY | 4 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE, TWO, THREE, AND FOUR LINKED |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE THREE |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC AND |
| 1.0 DC |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC AND |
| 50.0 DC |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | EXPLOSION PROOF AND |
| FUNGUS RESISTANT AND |
| MOISTURE RESISTANT AND |
| SHOCK RESISTANT AND |
| VIBRATION RESISTANT |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
SPECIAL HANDLING FEATURE | MAGNETIC |
FRAGILITY FACTOR | MODERATELY RUGGED |
SPECIFICATION/STANDARD DATA | 12436-A15912 GOVERNMENT SPECIFICATION |